This product is UL Listed for testing a smoke detector’s function per NFPA 72 and for use with smoke alarms listed to UL standard 217 and 268 when used as follows: From a distance of 2 to 4 ft. (.6-1.2m) aim spray for 1-2 seconds at the vents or side of the detector. When using this product in an enclosed dispenser device only a ½-1 second spray is typically required to activate the alarm. Alarm will sound within 1-10 seconds if the detector functions properly unless the detector has a built-in delay circuit. Detectors with delay circuits should be sprayed 1 or 2 additional times to activated, detector should alarm for 10 to 15 seconds.